Article NameAnalysis of Boundary Conditions of Sustainable Ferrosontic Process Flow in 24 KW Chains of Generator Voltage of NPP Power Units
AuthorsS.А. Baran, V.V. Nechitajlov, V.V. Krasnokutskij
Address

Volgodonsk Engineering Technical Institute the branch of National Research Nuclear University “MEPhI”,

Lenin St., 73/94, Volgodonsk, Rostov region, Russia 347360

1 ORCID: 0000-0002-3232-4072

WoS Researcher ID: I-7933-2018

e-mail: bastr@rambler.ru

2 ORCID: 0000-0002-6795-2458

WoS Researcher ID: J-3646-2018

e-mail: VITIkafAE@mephi.ru

3 ORCID: 0000-0002-4498-2996

WoS Researcher ID: I-4045-2018

e-mail: leronil@mail.ru

AbstractThe network generator voltage is operated using with isolated neutral, and line-to-ground fault is not short circuit. Ground-fault protection more often works on signal, but in some cases shutdown network protection occurs. Analysis of the causes of power unit shutdowns by the action of ground-fault protection showed that some of them were false and occurred as a result of the appearance of stable ferroresonance processes in the circuit. Passing of ferroresonance processes is possible at a certain ratio of the parameters of the electrical circuit. The paper deals with the boundary values of the total inductance and capacitance of the circuit, in which a stable ferroresonance process can occur in the circuit, the parameters of the equivalent circuit of the NPP power unit are calculated, the oscillograms of processes in a single-phase ground fault are considered, the resistor is selected for effective grounding of the neutral.
Keywordsferroresonance, generator voltage, isolated neutral, voltage transformer, overvoltage
LanguageRussian
References

[1]    Baran S.A., Nechitajlov V.V., Krasnokutskij V.V Vozniknovenie ferrorezonansa v cepyax 24 kV generatornogo napryazheniya e`nergoblokov AE`S [Ferroerezonans Emergency in the 24 kW Generator Voltage Circuits of NPP Units] [Global Nuclear Safety]. 2018. № 2 (27). Р. 56-65 (in Russian).
[2]    Kalantarov P.L., Cejtlin L.A. Raschet induktivnostej [Calculation of Inductances]. Leningrad. Pub. Energoatomizdat [Electroatomizdat]. 1986. 488 p. (in Russian).
[3]    Alekseev V.G., Ziherman M.H. Ferrorezonans v setyax 6-10 kV [Ferroresonance in 6-10 kW Networks]. [Electric Stations], 1978. №1. P. 63-65. (in Russian).
[4]    Jel-Hatib A.I. Ferrorezonansny`e processy` v transformatorax napryazheniya sistem e`lektrosnabzheniya i sposoby` ix predotvrashheniya [Ferroresonance Processes in Voltage Transformers of Power Supply Systems and Ways to Prevent Them]. Dissertacija na soiskanie uchenoj stepeni kandidata tehnicheskih nauk [Theses of PhD in Engineering]. Donetsk. Pub. Donskoj politehnicheskij institute [Don Polytechnic Institute]. 1992. 28 p. (in Russian).
[5]    Selivanov V.N. Ispol`zovanie programmy` rascheta e`lektromagnitny`x processov ATR-EMPT v uchebnom processe [Using the Program for Calculating the Electromagnetic Processes ATP-EMPT in the Education Process] [Herald of the Bauman MSTU]. 2009. №.1. P. 107-112.
[6]    Ivanickiy V.A. Modelirovanie perenapryazhenij v setyax e`lektrosnabzheniya s izolirovannoj nejtral`yu [Modeling of Overvoltages in Power Supply Systems with Isolated Neutral] [Moscow: "Virage Center" Scientific Technical Enterprise]. 1986. 488 p.
[7]    Petrov O.A. Smeshhenie nejtrali pri pofazny`x otklyucheniyax i obry`vax faz v kompensirovannoj seti [The Neutral Bias for Phase-Out Tripping and Phase Failure in Compensated Network]. Elektricheskie stancii [Electric Stations]. 1972. № 9. P. 57-61. (in Russian).
[8]    Halilov F.H. Eshhe raz o dugovy`x perenapryazheniyax v raspredelitel`ny`x setyax 6-35 kV [Once Again about Arc Overvoltages in Distribution Networks 6-35 kW.]. Promyshlennaja energetika [Industrial Power Engineering]. 1985. № 11. P. 37-41. (in Russian).
[9]    Lihachev F.A. Zamy`kaniya na zemlyu v setyax s izolirovannoj nejtral`yu i s kompensaciej emkostny`x tokov [Ground Faults in Networks with Isolated Neutral and with Compensation of Capacitive Currents]. M. Pub. Energija [Energy]. 1971. 152 p. (in Russian).
[10]    Gindullina F.A., Goldshtejn V.G., Duzolzon A.A., Halilov F.H. Perenapryazheniya v seti 6-35 kV [Overvoltages in 6-35 kW Network]. M. Pub. Energoatomizdat [Electroatomizdat]. 1989. 192 p. (in Russian).
[11]    Sirota I.M., Bogachenko A.E. Zashhita ot zamy`kanij na zemlyu na storone generatornogo napryazheniya blokov generator-transformator, oxvaty`vayushhaya nejtral` generatora [Earth-Fault Protection on the Generator Voltage Side of Generator-Transformer Blocks Covering the Generator Neutral]. Kiev. Pub. IED AN USSR [IED Academy of Sciences of the Ukrainian SSR]. 1972. 21 p. (in Russian).
[12]    Halilov F.H., Evdokunin G.A., Poljakov V.S. etc. Zashhita setej 6-35 kV ot perenaprjazhenij [Protection of 6-35 kW Overvoltage Networks]. Sankt-Peterburg. Pub. Energoatomizdat [Electroatomizdat]. 2002. (in Russian).